Modbus TCPIP til 5 DI & 3 DO Rele kontakt

5 Input & 3 output(Relay: RL1/Form A, RL2/3 Form C) Isolated channels with ModbusTCP module

Varenummer: EX-9060-MTCP Kategori:

Beskrivelse

Interface:



  • Communication: 10/100 Based-T Ethernet

  • Protocol: Modbus/TCP, TCP/IP, UDP, ICMP and ARP

  • Led indication: Led for power and Ethernet link status

  • Isolation voltage 3750Vrms

Digital Input:



  • Input channels 5

  • Input type: single ended with common source/ ground


    • Dry contact :


      • logic level 1 (inactive) : open

      • logic level 0 (active): Close to GND

    • Wet contact :


      • logic level 0 (inactive) : +2VDC max

      • logic level 1 (active): +4V to 30VDC max

    • Logic level status can be inversed via ASCII/Modbus command

  • Counter Input: 500Hz counter input (32-bit+1-bit overflow)

Digital Output:



  • Output channels: 3 Relay output

  • Relay type: RL1/Form A, RL2/3 Form C

  • Relay contact rating: 0.6A/125Vac, 2A/30Vdc

  • Surge Strength: 500V

  • Operate Time: 3mS max

  • Release Time: 2mS max

  • Min Life: 5*10 ops

  • Pulse output: Each channel supports 500Hz pulse output

Power requirement:



  • Consumption: 1.8W

  • Power input: 10~30VDC (unregulated)

  • Humidity: 5~95% RH, non-condensing

Handlekurv